Ametek i Series User Manual Page 288

  • Download
  • Add to my manuals
  • Print
  • Page
    / 341
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 287
User Manual
274 i Series / iX Series
Test No.
Section
Subject
Test Limits
Comment
File Ref.
TVF301
Abnormal Steady State Limits for Voltage and Frequency
100V to 125V RMS, 360Hz to 800
Hz
Apply for 30 mins
FTVF301
TVF302
Abnormal Voltage Transients
400-1
400 Hz, Overvoltage Transients
Peak Voltage 180V RMS
Table TVF302-2 A-G
FTVF302-400-1
400-2
400 Hz, Undervoltage Transients
Low Voltage 45V RMS
Table TVF302-2 H-N
FTVF302-400-2
400-3
400 Hz, Combined Transient
45V RMS to 180V RMS
Table TVF302-2 O
FTVF302-400-3
360-1
360 Hz, Overvoltage Transients
Peak Voltage 180V RMS
Table TVF302-2 A-G
FTVF302-360-1
360-2
360 Hz, Undervoltage Transients
Low Voltage 45V RMS
Table TVF302-2 H-N
FTVF302-360-2
360-3
360 Hz, Combined Transient
45V RMS to 180V RMS
Table TVF302-2 O
FTVF302-360-3
600-1
600 Hz, Overvoltage Transients
Peak Voltage 180V RMS
Table TVF302-2 A-G
FTVF302-600-1
600-2
600 Hz, Undervoltage Transients
Low Voltage 45V RMS
Table TVF302-2 H-N
FTVF302-600-2
600-3
600 Hz, Combined Transient
45V RMS to 180V RMS
Table TVF302-2 O
FTVF302-600-3
800-1
800 Hz, Overvoltage Transients
Peak Voltage 180V RMS
Table TVF302-2 A-G
FTVF302-800-1
800-2
800 Hz, Undervoltage Transients
Low Voltage 45V RMS
Table TVF302-2 H-N
FTVF302-800-2
800-3
800 Hz, Combined Transient
45V RMS to 180V RMS
Table TVF302-2 O
FTVF302-800-3
TVF303
Abnormal Frequency Transients
1
Overfrequency Transients
High Frequency 800 Hz
Table TVF303-2 A-D
FTVF303-1
2
Underfrequency Transients
Low Frequency 360 Hz
Table TVF303-2 E-H
FTVF303-2
3
Combined Transient
360 Hz to 800 Hz
Table TVF303-2 I
FTVF303-3
TVF401
Emergency Limits for Voltage and Frequency
Perform Test TVF102
TVF501
No Tests
N/A to AC Utilization Equipment
TVF601
Power Failure (Single Phase)
400-1
115V RMS, 400 Hz nominal settings
0V for 7 seconds
Table TVF601-2
FTVF601-400-1
360-1
115V RMS, 360 Hz nominal settings
0V for 7 seconds
Table TVF601-2
FTVF601-360-1
600-1
115V RMS, 600 Hz nominal settings
0V for 7 seconds
Table TVF601-2
FTVF601-600-1
800-1
115V RMS, 800 Hz nominal settings
0V for 7 seconds
Table TVF601-2
FTVF601-800-1
TVF602
One Phase and Two Phase Power Failures
400-1
One Phase Power Failures
0V for 7 seconds
Table TVF602-2 A-F
FTVF602-400-1
400-2
Two Phase Power Failures
0V for 30 mins
Table TVF602-2 G-J
FTVF602-400-2
360-1
One Phase Power Failures
0V for 7 seconds
Table TVF602-2 A-F
FTVF602-360-1
360-2
Two Phase Power Failures
0V for 30 mins
Table TVF602-2 G-J
FTVF602-360-2
600-1
One Phase Power Failures
0V for 7 seconds
Table TVF602-2 A-F
FTVF602-600-1
600-2
Two Phase Power Failures
0V for 30 mins
Table TVF602-2 G-J
FTVF602-600-2
800-1
One Phase Power Failures
0V for 7 seconds
Table TVF602-2 A-F
FTVF602-800-1
800-2
Two Phase Power Failures
0V for 30 mins
Table TVF602-2 G-J
FTVF602-800-2
TVF603
Phase Reversal
Phase reversal done physically
FTVF603
Table SXF:
Test No.
Section
Subject
Test Limits
Comment
File Ref.
SXF101
Load and Current Harmonic Measurements
115V RMS, 60 Hz
FSXF101
SXF102
Steady State Limits for Voltage and Frequency
105V to 125V RMS, 59.75 to 60.25 Hz
Apply for 30 mins each test
FSXF102
SXF103
No Test, Done so test numbers coincide
Page view 287
1 2 ... 283 284 285 286 287 288 289 290 291 292 293 ... 340 341